电子科技 ›› 2021, Vol. 34 ›› Issue (11): 75-80.doi: 10.16180/j.cnki.issn1007-7820.2021.11.012

• • 上一篇    下一篇

级联H桥电力电子变压器控制参数优化

高尚1,姚磊1,李洋2,李睿欣1   

  1. 1.上海理工大学 机械工程学院,上海 200093
    2.中国电力科学研究院有限公司 新能源与储能运行控制国家重点实验室,北京 100192
  • 收稿日期:2020-07-15 出版日期:2021-11-15 发布日期:2021-11-16
  • 作者简介:高尚(1995-),女,硕士研究生。研究方向:电力电子变压器稳定性。|姚磊(1983-),男,博士,讲师。研究方向:超导故障限流器智能电表。
  • 基金资助:
    国家自然科学基金(51707121)

Control Parameter Optimization of Cascaded H-Bridge Power Electronic Transformer

GAO Shang1,YAO Lei1,LI Yang2,LI Ruixin1   

  1. 1. School of Mechanical Engineering, University of Shanghai for Science and Technology,Shanghai 200093,China
    2. State Key Laboratory of Operation and Control of Renewabre Energy and Storage,China Electric Power Research Institute,Beijing 100192,China
  • Received:2020-07-15 Online:2021-11-15 Published:2021-11-16
  • Supported by:
    National Natural Science Foundation of China(51707121)

摘要:

PET作为分布式能源的重要环节,受到广泛的关注。由于非线性元件的存在,PET网侧电流谐波含量较高。文中以基于PR控制的CHB-PET为研究对象,采用电压外环和电流内环的双闭环控制策略,对CHB-PET进行参数优化。仿真结果表明,改变PR控制器的比例系数与谐振系数,网侧电流谐波含量也会随之改变。当比例系数保持不变,谐振系数从1 000变为100时,网侧电流谐波含量从3.24%下降到3.20%;当谐振系数保持不变,比例系数从50变为25时,网侧电流谐波含量从3.20%降为2.54%。由结果可知,相比于谐振系数,比例系数对网侧电流谐波含量的灵敏度更高。

关键词: 级联H桥, 电力电子变压器, 双闭环控制, 比例系数, 谐振系数, 谐波滤除, FFT分析, 总谐波失真

Abstract:

As an important part of distributed energy, PET has received widespread attention. Due to the existence of nonlinear components, the harmonic content of PET network side current is relatively high. In this study, CHB-PET based on the PR control is the research object, and the double closed-loop control strategy of voltage outer loop and current inner loop is adopted to optimize the parameters of CHB-PET. The simulation results show that changing the proportional coefficient and resonance coefficient of the PR controller will also change the harmonic content of the grid-side current. When the proportional coefficient remains unchanged and the resonance coefficient changes from 1 000 to 100, the harmonic content of the grid side decreases from 3.24% to 3.20%. Similarly, when the resonance coefficient remains unchanged and the proportional coefficient changes from 50 to 25, the harmonic content of grid side current decreases from 3.20% to 2.54%. The results show that compared with the resonance coefficient, the proportional coefficient is more sensitive to the harmonic content of the grid-side current.

Key words: cascaded-H bridge, power electronic transformer, double closed loop control, proportional coefficient, resonance coefficient, harmonic filtering, FFT analysis, total harmonic distortion